IS:5290 Type A landing valves for wet riser and hydrant networks — single and double outlet in gun metal or stainless steel.
For wet riser, yard hydrant and internal hydrant systems requiring IS:5290 Type A compliant landing valves.
Standards: Conforming to IS:5290, Type A
Technical Specifications
| Specification | Detail |
|---|---|
| Size | 63 mm / 75 mm / 80 mm (also 38 / 50 mm) |
| Inlet | 3" or 4" NB flanged (single outlet) |
| Outlet | Female instantaneous |
| Material | Gun metal / Stainless steel |
| Hand wheel | Grey cast iron |
| Body hydrostatic test | 23 kgf/Cm² |
| Seat water-tightness test | 14 kgf/Cm² |
| Flow test | 900 LPM discharge at 7 kgf/Cm² |
Key Highlights
- Single and double (Y) outlet configurations
- Gun metal and stainless steel options
- IS:5290 Type A compliant
- Also supply inlet breeching (2 / 3 / 4 way) and RRL hose Type A & B